32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

32$per unit

 

Product selection:

Specifications

(Type C, Type D)

number of polesLeakage

 RCD only

communication
16AMCB 1PLeakage protection 30mA485+dry contact
25AMCB 2PLeakage protection 100mADry wet contact+ reclosing
32AMCB 3PLeakage protection 300mAAutomatic reclosing
40AMCB 4P/WIFI(tuya
63ARCD 1P+N//

External dimensions

32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

Wiring instructions

Communication cables require the use of twisted pair shielded wires 2*0.5 mm²

32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker 32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker 32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

technical parameter

  1. Normal working conditions

1.1. Surrounding air temperature

1.1.1.    The upper limit value does not exceed+40 ℃

1.1.2.  The lower limit value shall not be lower than -5 ℃

1.1.3.  The average value within 24 hours shall not exceed+35 ℃

1.1.4.  Extreme operating temperature -25 ℃~+70 ℃

1.2. above sea level

1.2.1.  The altitude of the installation location shall not exceed 3000 meters

1.3. Atmospheric conditions

1.3.1. When the ambient air temperature is+40 ℃, the relative humidity of the air does not exceed 50%, and there can be higher relative humidity at lower temperatures

(For example, 90% humidity at 20 ℃)

1.4. class of pollution

1.4.1.  The pollution level used by the protector is level 2, which means that in general, there is only non-conductive pollution, but occasional transient conductive pollution caused by condensation can be expected

1.5. mounting classes

1.5.1.  mounting classes Ⅱ 、Ⅲ

2.parameter

2.1.rated voltageAC230V/400V

2.2. Current shell frame63A

2.3. breaking capacity: Ics is 6000A

2.4. Rated current InIn  16A 25A 32A 40A 50A 63A

2.5. Life: Mechanical lifespan of 10000 on-off cycles, electrical lifespan of 6000 on-off cycles

2.6. wiring:Using clamp connection terminals

2.6.1.   The cross-sectional area of the wire is 25  mm²

4.2.7. setset on the standard 35.5×7.5mm guide rail.

4.2.8. SPD:

4.2.8.1.  The over current trip characteristics of the protector when the ambient air temperature is between 30-35 ℃ (i.e. without temperature compensation) are shown in the table below

numberType of over current instantaneous release deviceRated current of circuit breaker InInitial stateTest currentset timeExpected results
1BCDIn63Acold1.13In≥1hnot trip
In>63A≥2h
2BCDIn≤63Ahot1.45In≤1htrip
In>63A≤2h
3BCDIn≤32Acold2.55In1s(t(60strip
In>32A1s<t<120s
4Ballcold3In≥0.1snot trip
C5In
D10In
5Ballcold5In<0.1strip
C10In
D20In

2.9. power

2.9.1.  standby power:<5W

2.9.2.  Synchronization power:<15W

2.9.3.  opening power:<15W

2.10. Minimum operating voltage: 70VAC

32*63*1P*6**AC230 Internet connected intelligent WIFI remote control intelligent circuit breaker,Motor Circuit Breaker

note

 

  1. The circuit breaker should not be affected by rainwater during transportation and storage, and the product should be stored in a well ventilated area.
  2. During use, dust and dirt should be regularly removed, and it is best to use a face mask to expose only the handle part of the circuit breaker.
  3. Before use, check whether the basic technical data on the nameplate or mark meets the requirements. The protection characteristics of this circuit breaker are determined by the manufacturer

During use, it cannot be disassembled or adjusted arbitrarily.

  1. The neutral wire must not be connected incorrectly.
  2. Before use, the connecting screw must be tightened to avoid poor contact and damage to the product.
  3. The setting temperature of this series of circuit breakers is 30+5 ℃. If multiple circuit breakers are installed in the same sealed box, they should be used with reduced capacity

The coefficient is 0.8