technical parameter 

Purpose:

 

The GSM8-32 and GSM8-80 series motor protection circuit breakers have the following purposes:

 

The GSM8-32 series motor protection circuit breaker is mainly used in circuits with AC 50Hz/60Hz, rated working voltage up to 690V, and rated working current of 0.1A~32A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for breaking during infrequent starting and operation. It can also be used as an isolator.

 

The GSM ⁸ -80 series motor protection circuit breaker is mainly used in circuits with AC 50H2/60Hz, rated working voltage up to 690V, and rated working current of 25A~80A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for infrequent starting and operation disconnection. It can also be used as an isolator.

GSM8 series accessories: expanding the number of auxiliary contacts, providing auxiliary signals, real-time monitoring, and connecting or disconnecting control circuits.

 

[Factory Direct Sales] GSM8 Series Motor Protection Circuit Breaker GSM8-3201

GSM8-32 Circuit Breaker

Basic technical parameter

usage category AC-3
Poles size

electric current

32A
Rated insulation voltage Ui AC 690V
Rated voltage Ue AC 690V
Rated current Ie 0.1~32A
 

Operational performance

 

Operating frequency (times/h) 120
Number of power on operation cycles (times) 60000
Number of non powered operation cycles (times) 60000

operating characteristic parameter

Delay protection feature

Serial Number Test current appointed time start state Expected results p.s.
a 1.05In t≤2h Cold Do not drop out
b 1.2In t<2h Hot Drop out Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds

 

C 1.5In t<4min Hot Drop out Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds

Instantaneous protection feature

Serial Number Test current appointed time start state Expected results
d 7.68In(In≤0.25) t≤0.2s Cold Do not  drop out
9.6In(In>0.25) t≤0.2s Cold Do not drop out
e 11.52In(In≤0.25) t<0.2s Cold Drop out
14.4In(In>0.25) t<0.2s Cold Drop out

Phase failure protection feature

Serial number Test current appointed time start state Expected results
f 2 pole1.0In/1pole0.9In t≤2h Cold Do not drop out
g 2pole1.15In/1pole without power t<2h Hot Drop out Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds

Short circuit breaking capacity

Release current Setting range code Current Setting range code( A Rated current(A) Short circuit breaking capacity(Ue:415V) Short circuit breaking capacity(Ue:690V)
Extreme short-circuit breaking Icu(KA) Movement short circuit breaking los(KA) Extreme short-circuit breaking Icu(KA) Movement short circuit breaking lcs(KA
01 0.1~0.16 0.16 50 50 3 2.25
02 0.16~025 0.25 50 50 3 2.25
03 0.25~0.4 0.4 50 50 3 2.25
04 0.4~0.63 0.63 50 50 3 2.25
05 0.63~1 1 50 50 3 2.25
06 1~1.6 1.6 50 50 3 2.25
07 1.6~2.5 2.5 50 50 3 2.25
08 2.5~4 4 50 50 3 2.25
10 4~6.3 6.3 50 50 3 2.25
14 6~10 10 50 50 3 2.25
16 9~14 14 15 7.5 3 2.25
20 13~18 18 15 7.5 3 2.25
21 17~23 23 15 6 3 2.25
22 20~25 25 15 6 3 2.25
32 24~32 32 10 5 3 2.25

GSM8-80 Circuit Breaker

 

Basic technical parameter

Current specification code 40、63、80
Rated operational current le 40A、63A、80A
Rated current of shell level 80A
Rated insulation voltage Ui 690V
Rated impulse withstand voltage Uimp 6KV
 

Operational performance

Operating frequency (times/h) 120
Mechanical lifespan powered on (times) 10000
Mechanical lifespan without power supply (times) 15000

operating characteristic parameter

 

 

 

protecting time-delay

Serial number Test current appointed time start state Expected results p.s. Temperature
a 1.05In t≤2h Cold Do not drop out Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds

 

+20±2℃
b 1.2In t<2h Hot Drop out

Instantaneous protection feature

Serial number Test current appointed time start state Expected results p.s. Temperature
c 9.6In t≤0.2s Cold Do not drop out This test is only applicable to the rated working current In
d 14.4In t<0.2s Cold Drop out

Short circuit breaking capacity

Code for current setting range of release device Current setting range(A) Rated current

(A)

Short circuit breaking capacity(Ue:415V)                     Short circuit breaking capacity(Ue:690V)
Extreme short-circuit breaking Icu(KA) Running short circuit breaker lcs(KA) Extreme short-circuit breaking lcu(KA) Running short circuit breaker lcs(KA
40 25~40 40 35 18 4 3
63 40~63 63 35 18 4 3
80 56~80 80 15 8 4 2