technical parameter
Purpose:
The GSM8-32 and GSM8-80 series motor protection circuit breakers have the following purposes:
The GSM8-32 series motor protection circuit breaker is mainly used in circuits with AC 50Hz/60Hz, rated working voltage up to 690V, and rated working current of 0.1A~32A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for breaking during infrequent starting and operation. It can also be used as an isolator.
The GSM ⁸ -80 series motor protection circuit breaker is mainly used in circuits with AC 50H2/60Hz, rated working voltage up to 690V, and rated working current of 25A~80A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for infrequent starting and operation disconnection. It can also be used as an isolator.
GSM8 series accessories: expanding the number of auxiliary contacts, providing auxiliary signals, real-time monitoring, and connecting or disconnecting control circuits.
GSM8-32 Circuit Breaker:
Basic technical parameter
usage category | AC-3 | |
Poles size
electric current |
32A | |
Rated insulation voltage Ui | AC 690V | |
Rated voltage Ue | AC 690V | |
Rated current Ie | 0.1~32A | |
Operational performance
|
Operating frequency (times/h) | 120 |
Number of power on operation cycles (times) | 60000 | |
Number of non powered operation cycles (times) | 60000 |
operating characteristic parameter
Delay protection feature
Serial Number | Test current | appointed time | start state | Expected results | p.s. |
a | 1.05In | t≤2h | Cold | Do not drop out | |
b | 1.2In | t<2h | Hot | Drop out | Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds
|
C | 1.5In | t<4min | Hot | Drop out | Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds |
Instantaneous protection feature
Serial Number | Test current | appointed time | start state | Expected results | |
d | 7.68In(In≤0.25) | t≤0.2s | Cold | Do not drop out | – |
9.6In(In>0.25) | t≤0.2s | Cold | Do not drop out | – | |
e | 11.52In(In≤0.25) | t<0.2s | Cold | Drop out | |
14.4In(In>0.25) | t<0.2s | Cold | Drop out | – |
Phase failure protection feature
Serial number | Test current | appointed time | start state | Expected results | |
f | 2 pole1.0In/1pole0.9In | t≤2h | Cold | Do not drop out | |
g | 2pole1.15In/1pole without power | t<2h | Hot | Drop out | Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds |
Short circuit breaking capacity
Release current Setting range code | Current Setting range code( A | Rated current(A) | Short circuit breaking capacity(Ue:415V) | Short circuit breaking capacity(Ue:690V) | ||
Extreme short-circuit breaking Icu(KA) | Movement short circuit breaking los(KA) | Extreme short-circuit breaking Icu(KA) | Movement short circuit breaking lcs(KA | |||
01 | 0.1~0.16 | 0.16 | 50 | 50 | 3 | 2.25 |
02 | 0.16~025 | 0.25 | 50 | 50 | 3 | 2.25 |
03 | 0.25~0.4 | 0.4 | 50 | 50 | 3 | 2.25 |
04 | 0.4~0.63 | 0.63 | 50 | 50 | 3 | 2.25 |
05 | 0.63~1 | 1 | 50 | 50 | 3 | 2.25 |
06 | 1~1.6 | 1.6 | 50 | 50 | 3 | 2.25 |
07 | 1.6~2.5 | 2.5 | 50 | 50 | 3 | 2.25 |
08 | 2.5~4 | 4 | 50 | 50 | 3 | 2.25 |
10 | 4~6.3 | 6.3 | 50 | 50 | 3 | 2.25 |
14 | 6~10 | 10 | 50 | 50 | 3 | 2.25 |
16 | 9~14 | 14 | 15 | 7.5 | 3 | 2.25 |
20 | 13~18 | 18 | 15 | 7.5 | 3 | 2.25 |
21 | 17~23 | 23 | 15 | 6 | 3 | 2.25 |
22 | 20~25 | 25 | 15 | 6 | 3 | 2.25 |
32 | 24~32 | 32 | 10 | 5 | 3 | 2.25 |
GSM8-80 Circuit Breaker
Basic technical parameter
Current specification code | 40、63、80 | |
Rated operational current le | 40A、63A、80A | |
Rated current of shell level | 80A | |
Rated insulation voltage Ui | 690V | |
Rated impulse withstand voltage Uimp | 6KV | |
Operational performance |
Operating frequency (times/h) | 120 |
Mechanical lifespan powered on (times) | 10000 | |
Mechanical lifespan without power supply (times) | 15000 |
operating characteristic parameter
protecting time-delay
Serial number | Test current | appointed time | start state | Expected results | p.s. | Temperature |
a | 1.05In | t≤2h | Cold | Do not drop out | Immediately after test a, the current stabilizes and rises to the specified value within 5 seconds
|
+20±2℃ |
b | 1.2In | t<2h | Hot | Drop out |
Instantaneous protection feature
Serial number | Test current | appointed time | start state | Expected results | p.s. | Temperature |
c | 9.6In | t≤0.2s | Cold | Do not drop out | This test is only applicable to the rated working current In | |
d | 14.4In | t<0.2s | Cold | Drop out |
Short circuit breaking capacity
Code for current setting range of release device | Current setting range(A) | Rated current
(A) |
Short circuit breaking capacity(Ue:415V) Short circuit breaking capacity(Ue:690V) | |||
Extreme short-circuit breaking Icu(KA) | Running short circuit breaker lcs(KA) | Extreme short-circuit breaking lcu(KA) | Running short circuit breaker lcs(KA | |||
40 | 25~40 | 40 | 35 | 18 | 4 | 3 |
63 | 40~63 | 63 | 35 | 18 | 4 | 3 |
80 | 56~80 | 80 | 15 | 8 | 4 | 2 |