technical parameter 

Purpose:

 

The GSM8-32 and GSM8-80 series motor protection circuit breakers have the following purposes:

 

The GSM8-32 series motor protection circuit breaker is mainly used in circuits with AC 50Hz/60Hz, rated working voltage up to 690V, and rated working current of 0.1A~32A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for breaking during infrequent starting and operation. It can also be used as an isolator.

 

The GSM ⁸ -80 series motor protection circuit breaker is mainly used in circuits with AC 50H2/60Hz, rated working voltage up to 690V, and rated working current of 25A~80A. It is used for overload, short circuit, and three-phase unbalance protection of three-phase motors, as well as for infrequent starting and operation disconnection. It can also be used as an isolator.

GSM8 series accessories: expanding the number of auxiliary contacts, providing auxiliary signals, real-time monitoring, and connecting or disconnecting control circuits.

 

[Factory Direct Sales] GSM8 Series Motor Protection Circuit Breaker GSM8-3201

GSM8-32 Circuit Breaker

Basic technical parameter

usage categoryAC-3
Poles size

electric current

32A
Rated insulation voltage UiAC 690V
Rated voltage UeAC 690V
Rated current Ie0.1~32A
 

Operational performance

 

Operating frequency (times/h)120
Number of power on operation cycles (times)60000
Number of non powered operation cycles (times)60000

operating characteristic parameter

Delay protection feature

Serial NumberTest currentappointed timestart stateExpected resultsp.s.
a1.05Int≤2hColdDo not drop out
b1.2Int<2hHotDrop outImmediately after test a, the current stabilizes and rises to the specified value within 5 seconds

 

C1.5Int<4minHotDrop outImmediately after test a, the current stabilizes and rises to the specified value within 5 seconds

Instantaneous protection feature

Serial NumberTest currentappointed timestart stateExpected results
d7.68In(In≤0.25)t≤0.2sColdDo not  drop out
9.6In(In>0.25)t≤0.2sColdDo not drop out
e11.52In(In≤0.25)t<0.2sColdDrop out
14.4In(In>0.25)t<0.2sColdDrop out

Phase failure protection feature

Serial numberTest currentappointed timestart stateExpected results
f2 pole1.0In/1pole0.9Int≤2hColdDo not drop out
g2pole1.15In/1pole without powert<2hHotDrop outImmediately after test a, the current stabilizes and rises to the specified value within 5 seconds

Short circuit breaking capacity

Release current Setting range codeCurrent Setting range code( ARated current(A)Short circuit breaking capacity(Ue:415V)Short circuit breaking capacity(Ue:690V)
Extreme short-circuit breaking Icu(KA)Movement short circuit breaking los(KA)Extreme short-circuit breaking Icu(KA)Movement short circuit breaking lcs(KA
010.1~0.160.16505032.25
020.16~0250.25505032.25
030.25~0.40.4505032.25
040.4~0.630.63505032.25
050.63~11505032.25
061~1.61.6505032.25
071.6~2.52.5505032.25
082.5~44505032.25
104~6.36.3505032.25
146~1010505032.25
169~1414157.532.25
2013~1818157.532.25
2117~232315632.25
2220~252515632.25
3224~323210532.25

GSM8-80 Circuit Breaker

 

Basic technical parameter

Current specification code40、63、80
Rated operational current le40A、63A、80A
Rated current of shell level80A
Rated insulation voltage Ui690V
Rated impulse withstand voltage Uimp6KV
 

Operational performance

Operating frequency (times/h)120
Mechanical lifespan powered on (times)10000
Mechanical lifespan without power supply (times)15000

operating characteristic parameter

 

 

 

protecting time-delay

Serial numberTest currentappointed timestart stateExpected resultsp.s.Temperature
a1.05Int≤2hColdDo not drop outImmediately after test a, the current stabilizes and rises to the specified value within 5 seconds

 

+20±2℃
b1.2Int<2hHotDrop out

Instantaneous protection feature

Serial numberTest currentappointed timestart stateExpected resultsp.s.Temperature
c9.6Int≤0.2sColdDo not drop outThis test is only applicable to the rated working current In
d14.4Int<0.2sColdDrop out

Short circuit breaking capacity

Code for current setting range of release deviceCurrent setting range(A)Rated current

(A)

Short circuit breaking capacity(Ue:415V)                     Short circuit breaking capacity(Ue:690V)
Extreme short-circuit breaking Icu(KA)Running short circuit breaker lcs(KA)Extreme short-circuit breaking lcu(KA)Running short circuit breaker lcs(KA
4025~4040351843
6340~6363351843
8056~808015842