4~35$ basic on specific type

basic information

Installation categoryWorking and installation conditions
Type
class of pollution3
Compliant with standardsGB/T 14048.1/IEC 60947-1、GB/T 14048.4/IEC 60947-4-1、 GB/T 14048.5/IEC 60947-5-1、GB 21518
authenticationCE、CCC
Shell protection levelNXCF-06M~38 is IP20( Only applicable to the front side);NXCF-40~100 is IP10 ;NXCF-120~630 is IP00
Surrounding air temperatureThe maximum working temperature is -35 ℃~+70 ℃, the normal working temperature is -5 ℃~+40 ℃, and the average value within 24 hours does not exceed+35 ℃. If not used within the normal operating temperature range, please refer to the appendix “Instructions for Non normal Environment Use” for details
above sea levelNot exceeding 2000m, if not used within this range, refer to the Appendix “Instructions for Abnormal Environment Use”
Atmospheric conditionsWhen the maximum temperature is+70 ℃, the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at+20 ℃. Special measures should be taken for occasional condensation caused by humidity changes.
Installation conditionsThe inclination angle between the installation surface and the vertical surface shall not exceed ± 5 °
Shock and vibrationThe product should be installed and used in a place without significant shaking, impact, and vibration

1 Scope of application

The all-new NXCF series AC contactor has a novel appearance and compact structure. Mainly used for frequent starting and control of AC motors, remote connection and disconnection of circuits, and can be combined with appropriate thermal overload relays to form electromagnetic starters.

Compliant with standards:GB/T 14048.1/IEC 60947-1、GB/T 14048.4/IEC 60947-4-1、 GB/T 14048.5/IEC60947 -5-1、GB 21518.

new design high quality NXC-06 220V 50Hz 220V 6A

2 main parameter

2.1 Rated working current Ie:6A~630A

2.2 Rated working voltage Ue:220V~690V

2.3 Rated insulation voltage:690V(NXCF-06(M)~100)、1000V(NXCF-120~630)

2.4 number of poles:3P、4P( 仅 NXCF-06M~12M)

2.5 Coil control method:AC(NXCF-06(M)~225)、DC(NXCF-06M~12M)、AC/DC(NXCF-265~630)

2.6 Installation method:NXCF-06M~100 Installation of card rails and screws、NXCF-120~630 Screw installation

new design high quality NXC-06 220V 50Hz 220V 6A

3 Working and installation conditions

Installation categoryWorking and installation conditions
Type
class of pollution3
Compliant with standardsGB/T 14048.1/IEC 60947-1、GB/T 14048.4/IEC 60947-4-1、 GB/T 14048.5/IEC 60947-5-1、GB 21518
authenticationCE、CCC
Shell protection levelNXCF-06M~38 is IP20( Only applicable to the front side);NXCF-40~100 is IP10 ;NXCF-120~630 is IP00
Surrounding air temperatureThe maximum working temperature is -35 ℃~+70 ℃, the normal working temperature is -5 ℃~+40 ℃, and the average value within 24 hours does not exceed+35 ℃. If not used within the normal operating temperature range, please refer to the appendix “Instructions for Non normal Environment Use” for details
above sea levelNot exceeding 2000m, if not used within this range, refer to the Appendix “Instructions for Abnormal Environment Use”
Atmospheric conditionsWhen the maximum temperature is+70 ℃, the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as reaching 90% at+20 ℃. Special measures should be taken for occasional condensation caused by humidity changes.
Installation conditionsThe inclination angle between the installation surface and the vertical surface shall not exceed ± 5 °
Shock and vibrationThe product should be installed and used in a place without significant shaking, impact, and vibration

new design high quality NXC-06 220V 50Hz 220V 6A

Model Description

Note: The 06A-100A specification product comes with 1 normally open and 1 normally closed auxiliary contact.

Model example: NXCF-12 220V indicates that the rated working current of the contactor is 12A when the main circuit voltage is 380V/400V under the AC-3 usage category. Each contactor body is equipped with 1 normally open and 1 normally closed auxiliary contact, and the coil control voltage is 220V AC with a frequency of 50Hz.

NXCF  Series Selection Table for AC Contactors.

new design high quality NXC-06 220V 50Hz 220V 6A

Main Parameters and Technical Performance

Main circuit parameters and technical performance

Contactor modelNXCF-06NXCF-09NXCF-12NXCF-16NXCF-18NXCF-22
Shell level06~1618~22
Agreed free air heating current Ith(A)202025253232
Rated insulation voltage Ui(V)
Rated impulse withstand voltage Ui mp(kV)8
Rated connection capacitycurrent on:10×Ie(AC-3) or 12×Ie(AC-4)
Rated breaking capacityConnect breaking current:8×Ie(AC-3) or 0×Ie(AC-4)
Rated working current

Ie(A)

AC-1202025253232
220V/230VAC-36912161822
AC-4691216    –1822
380V/400VAC-36912161822
AC-46912121818
660V/690VAC-33.86.68.98.91214
AC-43.86.68.98.91212
Rated control powerAC-3(kW)220V/230V1.52.23345.5
380V/400V2.245.57.57.511
660V/690V35.57.57.51011
Electrical lifespan (10000 cycles)AC-3120
AC-4The specific information is in the electrical life curve chart
Mechanical lifespan (1000 cycles)12 000
Main contact structure type3 normally open
SCPD Used fusesgG20gG20gG25gG25gG32gG32
Matching thermal overload relayTypeNXRF-25
Number of built-in auxiliary contacts3P1 open 1 close
4P
control circuit Contactor modelNXCF-06NXCF-09NXCF-12NXCF-16NXCF-18NXCF-22
Main circuit wiringCable connection (mm²)Prefabricated flexible wire11~41.5~6
21~2.51.5~4
Hard wire11~41.5~6
21~41.5~6
Tightening screw sizeM3.5M3.5
Tightening torque (N·m)1.21.2
Control circuit connectionCable connection (mm²)Prefabricated flexible wire11~1.5
21~1.5
Hard wire11~1.5
21~1.5
Tightening screw sizeM3.5
Tightening torque (N·m)1.2
Contactor modelNXCF-06NXCF-09NXCF-12NXCF-16NXCF-18NXCF-22
Coil control power supplyInter flow 50Hz24、36、42、48、110、120、127、220、230、240、277、380、400、415、440、460、480、525、600、660
continuous current
range of motionPull-in(70%~120%)Us
Released(20%~65%)Us
Average power consumption of coil (VA)Open50~70
Hold≤ 9.0≤ 9.5
Heat loss rate(W)alternating1~3
constant current
Main contact action time(ms)close12~40
Break4~25
TypeAmaxBmaxCmaxDmaxEmaxFmaxGmaxa1b1C1a2b2C2ef
NXCF-06~1645.5758870126.5146.59035±0.3148±0.31Φ4.510.67.8
NXCF-18~2245.5758870126.5146.59035±0.3148±0.31Φ4.511.49.2
NXCF-25~3856.5879381131.5151.59540±0.3148±0.31Φ4.514.210.6
NXCF-40~6577129118102156.5176.512140±0.28105±0.57Φ6.564105Φ6209.5
NXCF-75~10087132127112165.5185.512940±0.28105±0.57Φ6.574112Φ6.22413

new design high quality NXC-06 220V 50Hz 220V 6A

1Instructions for use in abnormal environments

Explanation of using correction factors in high-altitude areas

  • The GB/T 14048.1 standard specifies the relationship between altitude and impulse withstand voltage. When the altitude is ≤ 2000m, it has no significant impact on product performance.
  • When the altitude is greater than 2000m, the air cooling effect and the decrease in rated impulse withstand voltage must be considered, so the manufacturer needs to negotiate with the user for design or use.
  • The following table provides the correction factors for the rated impulse withstand voltage and rated working current at an altitude greater than 2000m and with the rated working voltage unchanged.
above sea level(m)2000300040005000
Rated impulse withstand voltage correction factor10.880.780.7
Rated working current correction factor10.920.90.85

     

    • After parallel connection of poles, considering the distribution of long-term unstable currents, the rated current of parallel poles needs to be adjusted, as shown in the table below:
    Parallel series234
    correction factor1.62.252.8

    Note: If the product is applied in a dusty environment,Please select and install a dust cover AXC-1、AXC-2、AXC-3、AXC-4。